ABB ACS580 Series - Parameter Settings for External Braking Chopper and Resistor

ABB ACS580 Series
468 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reference resistor typesP
BRmax
R
max
R
min
ACS580-01-…
kWohmohm
SAFUR80F5007811.54.3099A-6
SAFUR80F5001078.54.3125A-6
SAFUR80F5001287.03.2144A-6
SAFUR125F5001575.82.2192A-6
2xSAFUR200F5001884.82.2242A-6
2xSAFUR200F5002284.02.2271A-6
Symbols
= minimum allowed brake resistor that can be connected to the brake chopper
R
min
= maximum allowed brake resistor that allows
P
BRmax
R
max
= maximum braking capacity of the drive, must exceed the desired braking power.
P
BRmax
WARNING!
Do not use a brake resistor with a resistance below the minimum value
specified for the particular drive. The drive and the internal chopper are not
able to handle the overcurrent caused by the low resistance.
Parameter settings for external braking chopper and resistor
Disable the overvoltage control of the drive with parameter 30.30 Overvoltage
control.
Disable parameter 43.06 Braking chopper function as parameter group 43 Brake
chopper is used for internal braking chopper and resistor only.
For more information, see
NBRA-6xx Braking Choppers Installation and start-up
guide
(3AFY58920541 [English]) and
ACS-BRK Brake Units Installation and start-up
guide
(3AFY61514309 [English]).
408 Resistor braking