Cu cable typeFrame sizeACS580-01-…
AWG/kcmil
2×250 MCMR9271A-6
Temperature: For IEC, select a cable rated for at least 70 °C maximum permissible
temperature of conductor in continuous use. For North America, power cables
must be rated for 75 °C (167 °F) or higher.
Note: For drives with option +B056 (IP55, UL Type 12), select a cable rated for at
least 90 °C (194 °F) maximum permissible temperature of conductor in continuous
use.
Note: For drives with option +B063 or +B066 (IP66, UL Type 4X), with voltage rating
575 V AC (-6) running above 40 °C ambient temperature, select a cable rated of at
least 90 °C (194 °F) maximum permissible temperature of conductor in continuous
use.
Voltage: 600 V AC cable is accepted for up to 500 V AC.
Terminal and entry data for the control cables
■
IEC
Control cable entries, wire sizes and tightening torques (
T
) are given below.
Control cable entries and terminal sizesCable entriesFrame
size
DI, AI/O, AGND, RO, STO
terminals
+24V, DCOM, DGND, EXT.
24V terminals
Max cable
size
Holes
T
Wire size
T
Wire size
N·mmm
2
N·mmm
2
mmpcs
0.5…0.60.14…1.50.5…0.60.2…2.5173R1
0.5…0.60.14…1.50.5…0.60.2…2.5173R2
0.5…0.60.14…1.50.5…0.60.2…2.5173R3
0.5…0.60.14…1.50.5…0.60.2…2.5174R4, R4
v2
0.5…0.60.14…1.50.5…0.60.2…2.5173R5
0.5…0.60.14…2.50.5…0.60.14…2.5174R6
0.5…0.60.14…2.50.5…0.60.14…2.5174R7
0.5…0.60.14…2.50.5…0.60.14…2.5174R8
0.5…0.60.14…2.50.5…0.60.14…2.5174R9