--Pollution degree 2Pollution degree
(IEC/EN 60664-1)
60…106 kPa
0.6…1.05 atmo-
spheres
70…106 kPa
0.7…1.05 atmo-
spheres
70…106 kPa
0.7…1.05 atmo-
spheres
Atmospheric pressure
--Max. 1 mm (0.04 in)
(5…13.2 Hz), max.
7 m/s
2
(23 ft/s
2
)
(13.2…100 Hz) sinus-
oidal
Vibration (IEC 60068-2)
R1…R4 (ISTA 1A): Displacement, 25 mm
peak to peak, 14200 vibratory impacts
-Vibration (ISTA)
R5…R9 ISTA 3E): Random, overall Grms
level of 0.52
R1…R4 (ISTA 1A): Drop, 6 faces, 3 edges
and 1 corner
Not allowedShock/Drop (ISTA)
inmmWeight range
29.97600…10 kg (0…22 lb)
24.061010…19 kg (22…42 lb)
18.146019…28 kg (42…62 lb)
13.434028…41 kg (62…90 lb)
R5…R9 (ISTA 3E): Shock, incline impact:
1.1 m/s (3.61 ft/s)
Shock, rotational edge drop: 200 mm
(7.9 in)
1)
For symmetrically grounded TN-S systems, TT systems, and ungrounded or symmetrically
high-resistance grounded IT systems. See also section Limiting relay output maximum voltages at
high installation altitudes (page 125).
2)
For corner-grounded delta systems, midpoint-grounded delta systems and corner-grounded (via high
resistance) IT systems.
3)
IP66 (UL Type 4X) drive can be used outdoors if protected from the heat of the sun and indoors or
outdoors in a dusty environment.
Note: There are special considerations in corner-grounded installations above
2000 m. Contact your local ABB representative for further information.
Storage conditions
Store the drive in humidity controlled enclosed environments. Keep the drive in
its package.