WARNING!
If you disable the brake chopper by parameter, also disconnect the brake
resistor cable from the drive. Otherwise, there is a risk of resistor overheating
and damage.
Resistor braking, frames R4…R9
Planning the braking system
Frames R4…R9 need external brake choppers and resistors. The table below lists
suitable choppers and resistors.
IEC
Reference resistor types
1)
P
BRmax
R
max
R
min
Brake chop-
per
ACS580-
01-…
kWohmohm
3-phase
U
n
= 230 V
SAFUR125F500265.62.0NBRA-658089A-2
SAFUR125F500314.72.0NBRA-658115A-2
SAFUR200F500433.42.0NBRA-658144A-2
SAFUR200F500532.81.3NBRA-658171A-2
2xSAFUR210F575642.31.3NBRA-658213A-2
2xSAFUR210F575781.90.9NBRA-658276A-2
3-phase
U
n
= 400 or 480 V (380…415 V, 440…480 V)
Built in with the brake chopper3018.17.8ACS-BRK-D062A-4
Built in with the brake chopper4213.17.8ACS-BRK-D073A-4
Built in with the brake chopper5110.77.8ACS-BRK-D088A-4
SAFUR125F500638.71.3NBRA-658106A-4
SAFUR125F500777.11.3NBRA-658145A-4
SAFUR200F5001055.21.3NBRA-658169A-4
SAFUR200F5001264.31.3NBRA-658206A-4
2xSAFUR125F5001563.51.3NBRA-658246A-4
2xSAFUR210F5751872.91.3NBRA-658293A-4
2xSAFUR200F5002272.40.7NBRA-659363A-4
2xSAFUR200F5002841.90.7NBRA-659430A-4
1)
Other resistors can be used if they meet the minimum resistance value and required power values.
406 Resistor braking