Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a
heated, indoor, controlled environment
3)
. All printed circuit boards are conformal
coated.
Transportation
in the package
Storage
in the package
Operation
installed for
stationary use
--• 0…4000 m
(13123 ft) above
sea level
1)
• 0…2000 m (6561
ft) above sea
level
2)
Output derated
above 1000 m (3281
ft), see section Alti-
tude derat-
ing (page 282).
Installation site altitude
-40…+70 °C
(-40…+158 °F)
-40…+70 °C
(-40…+158 °F)
-15…+50 °C
(5…122 °F).
0…-15 °C (32…5 °F):
No frost allowed.
See section Electric-
al ratings (page 266).
Air temperature
Max. 95%Max. 95%5…95%Relative humidity
No condensation allowed. Maximum allowed relative humidity
is 60% in the presence of corrosive gases.
IEC 60721-3-2: 1997IEC 60721-3-1: 1997IEC 60721-3-3:
2002:
Classification of en-
vironmental condi-
tions - Part 3-3:
Classification of
groups of environ-
mental parameters
and their severities
- Stationary use of
weather protected
locations
Contamination levels
Class 2C2Class 1C2Class 3C2Chemical gases
Class 2S2Class 1S3 (packing
must support this,
otherwise 1S2)
Class 3S2. No con-
ductive dust al-
lowed.
Solid particles
350 Technical data