ABB ACS580 Series - Fuses (UL)

ABB ACS580 Series
468 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MCBs and MCCBsACS580-
01-…
SACE ordering
code for breaker
and release unit
Electronic
release
T
max
rating
T
max
frame
XT / T
class
Max.
short-
circuit
ABB type
1)
I
sc
AAAkA
N/AN/AN/AN/A12S 203P-B/C/Z 50046A-4
N/AN/AN/AN/A50S 803S-B/C 80062A-4
N/AN/AN/AN/A50S 803S-B/C 80073A-4
N/AN/AN/AN/A50S 803S-B/C 100088A-4
N/AN/AN/AN/A50S 803S-B/C 100089A-4
N/AN/AN/AN/A50S 803S-B/C 125106A-4
1SDA068555R1250250XT465XT4 L 250 Ekip LS/I
In=250 3p F F
145A-4
1SDA068555R1250250XT465XT4 L 250 Ekip LS/I
In=250 3p F F
169A-4
1SDA054141R1320320T465T4 L 320 PR221DS-LS/I
In=320 3p F F
206A-4
1SDA054365R1400400T565T5 L 400 PR221DS-LS/I
In=400 3p F F
246A-4
1SDA054420R1630630T565T5 L 630 PR221DS-LS/I
In=630 3p F F
293A-4
1SDA054420R1630630T565T5 L 630 PR221DS-LS/I
In=630 3p F F
363A-4
1SDA054420R1630630T565T5 L 630 PR221DS-LS/I
In=630 3p F F
430A-4
1)
Trip characteristic Z is recommended
Fuses (UL)
Fuses for branch circuit protection per NEC are listed below. ABB recommends
fast acting class T or faster fuses in the USA. Obey local regulations.
For IP66 (UL Type 4X) drives that include the disconnect and fuse option, no branch
circuit protection is required external to the drive. Fuses shown in this table are
included inside the drive.
Technical data 299