EasyManua.ls Logo

ABB ACS580 Series - Page 239

ABB ACS580 Series
468 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Make sure that
The control cables are connected to the correct terminals, and the terminals are
tightened to the correct torque.
If a drive bypass connection will be used: The direct-on-line contactor of the motor
and the drive output contactor are either mechanically and/or electrically interlocked,
that is, they cannot be closed at the same time. A thermal overload device must be
used for protection when bypassing the drive. Refer to local codes and regulations.
There are no tools, foreign objects or dust from drilling inside the drive.
The area in front of the drive is clean: the drive cooling fan cannot draw any dust or
dirt inside.
Drive covers and the terminal box cover of the motor are in place.
IP66 (UL Type 4X) drives: All cable gland and conduit fittings are tightened sufficiently
to prevent leaking into the drive. Cover and conduit box are installed and all screws
are torqued to 2.5 N·m (1.8 lbf·in). For outdoor installation, the drive is shaded from
direct sunlight to prevent excessive heating.
The motor and the driven equipment are ready for power-up.
Installation checklist 239

Table of Contents

Other manuals for ABB ACS580 Series

Related product manuals