UL (NEC)
Nominal output current (
I
2
) for the minimum switching
frequencies at 40 °C (+104 °F)
Nominal
output
ACS580-
01-…
Frame
size
16 kHz12 kHz8 kHz4 kHz2 kHz1 kHz
I
2
AAAAAAA
3-phase
U
1
= 200…240 V,
P
n
at
U
n
= 208/230 V, 60 Hz
3.33.74.14.64.64.64.604A6-2R1
4.85.35.96.66.66.66.606A6-2R1
5.46.06.77.57.57.57.507A5-2R1
7.68.59.410.610.610.610.610A6-2R1
12.013.414.916.716.716.716.7017A-2R1
15.717.920.824.224.224.224.2024A-2R2
20.022.826.530.830.830.830.8031A-2R2
29.133.339.346.246.246.246.2046A-2R3
37.242.55059595959059A-2R3
48.8566575757575075A-2R4
N/A354975757575075A-2R4 v2
51617288888888088A-2R5
N/A42.35890909090090A-2R4
667993114114114114114A-2R5
100114129143143143143143A-2R6
118135152169169169169169A-2R7
148169190211211211211211A-2R7
N/AN/AN/A273273273273273A-2R8
N/A274309343343343343343A-2R9
N/A317356396396396396396A-2R9