Maximum
I
peak
Maximum
I
2
t
ABB circuit breakerDrive
volume
Enclos-
ure min-
imum
volume
CB
voltage
CB max-
imum
current
Input
current
Frame
size
ACS580-
01-…
kA
A
2
s
65 kA @ 240 V
in
3
in
3
VAA
3-phase
U
1
= 500…600 V,
P
n
at
U
n
= 575 V, 60 Hz
31.5
1.2×10
6
XT4Vαβ025#********68416200600252.7R202A7-6
31.5
1.2×10
6
XT4Vαβ025#********68416200600253.9R203A9-6
31.5
1.2×10
6
XT4Vαβ025#********68416200600256.1R206A1-6
31.5
1.2×10
6
XT4Vαβ025#********68416200600259R209A0-6
31.5
1.2×10
6
XT4Vαβ025#********684162006002511R2011A-6
31.5
1.2×10
6
XT4Vαβ025#********684162006002517R2017A-6
31.5
1.2×10
6
XT4Vαβ050#********684162006005022R3022A-6
31.5
1.2×10
6
XT4Vαβ050#********1011162006005027R3027A-6
31.5
1.2×10
6
XT4Vαβ050#********1011162006005032R3032A-6
31.5
1.2×10
6
XT4Vαβ125#********20301620060012541R5041A-6
31.5
1.2×10
6
XT4Vαβ125#********20301620060012552R5052A-6
31.5
1.2×10
6
XT4Vαβ125#********20301620060012562R5062A-6
31.5
1.2×10
6
XT4Vαβ125#********20301620060012577R5077A-6
31.5
1.2×10
6
XT4Vαβ200#********33691890060020099R7099A-6
31.5
1.2×10
6
XT4Vαβ200#********336918900600200125R7125A-6
31.5
1.2×10
6
XT4Vαβ200#********385832400600250144R7144A-6
51.4
4.2×10
6
XT5Lαβ40A#********522632400600400192R9192A-6
51.4
4.2×10
6
XT5Lαβ40A#********522632400600400242R9242A-6
51.4
4.2×10
6
XT5Lαβ40A#********522632400600400271R9271A-6
See notes 1-9, 12-13 and 17 below
Notes for all drives except IP66 (UL Type 4X) with disconnect and fuse option:
1. Drives that have an enclosure minimum volume listed must be mounted in an
enclosure ≥ enclosure minimum volume specified in the tables above.
2. When multiple drives that have an enclosure minimum volume specified are
installed in the same enclosure, minimum volume of the enclosure is determined
by the largest enclosure minimum volume of the drives to be placed in the
enclosure, plus the volume(s) of each additional drive. i.e. for the 480 V R6 and
R3 drive select enclosure with the volume ≥ 16200+1011 = 17211 in
3
.
Technical data 305