Appendix I System Messages
I-10 3BSE 002 415R701 Rev A
Table I-9. Type 22, Code 9, 12, 13 and 20
Type Code Significance Data 1 Comments/Actions
22 9 100
101
109
110
113
Correct again after overload.
Overload.
Insufficient memory or memory error.
Clock change or overload.
Interpreter task begun before INIT of the process
communication has been completed. This message
needs no corrective action during the initialization.
12 This type of fault affects the
pulse counter and
positioning board
DSDP 140A and DSDP 150
Address = board address
100
101
102
103
104
105
106
107
108
109
Continue
The address jumpering of the positioning board and the
I/O address given on the PC element POS-A are
different. The positioning board is inactive.
The I/O address given on the PC element POS-A is
odd.
The address jumpering of the positioning board and the
I/O address given on the PC element POS-O are
different. The positioning board is inactive.
The I/O address given on the PC element POS-O is
odd.
The address jumpering of the positioning board and the
I/O address given on the PC element POS-L are
different. The positioning board is inactive.
The I/O address given on the PC element POS-L is
odd.
The address jumpering of the positioning board and the
I/O address given on the PC element PULSE-S are
different.
The I/O address given on the PC element PULSE-S is
odd.
The address jumpering of the positioning board and the
I/O address given on the PC element FREQ-SP are
different.
The I/O address of the PC element FREQ-SP is odd.