186
Signal and parameter list
Signal / Parameter name
min.
max.
def.
unit
10.17 Jog1 (jogging 1 command)
Binary signal for
Jog1. Selects speed reference set in FixedSpeed1 (23.02):
0 =
NotUsed default
1 =
DI1 1= Jog1 active, 0 = no Jog1
2 =
DI2 1= Jog1 active, 0 = no Jog1
3 =
DI3 1= Jog1 active, 0 = no Jog1
4 =
DI4 1= Jog1 active, 0 = no Jog1
5 =
DI5 1= Jog1 active, 0 = no Jog1
6 =
DI6 1= Jog1 active, 0 = no Jog1
7 =
DI7 1= Jog1 active, 0 = no Jog1
8 =
DI8 1= Jog1 active, 0 = no Jog1
9 =
DI9 1= Jog1 active, 0 = no Jog1, only available with digital extension board
10 =
DI10 1= Jog1 active, 0 = no Jog1, only available with digital extension board
11 =
DI11 1= Jog1 active, 0 = no Jog1, only available with digital extension board
12 =
MCW Bit11 1= Jog1 active, 0 = no Jog1, MainCtrlWord (7.01) bit 11
13 =
MCW Bit12 1= Jog1 active, 0 = no Jog1, MainCtrlWord (7.01) bit 12
14 =
MCW Bit13 1= Jog1 active, 0 = no Jog1, MainCtrlWord (7.01) bit 13
15 =
MCW Bit14 1= Jog1 active, 0 = no Jog1, MainCtrlWord (7.01) bit 14
16 =
MCW Bit15 1= Jog1 active, 0 = no Jog1, MainCtrlWord (7.01) bit 15
Notes:
Jog2 (10.18) overrides Jog1 (10.17)
CommandSel (10.01) = Local I/O:
The drive has to be in state RdyRun (RdyRef is still zero). When Jog1 command is given the drives sets
automatically RampOutZero = RampHold = RampInZero = 0 [see MainCtrlWord (7.01)] and goes into
state Running and turns with speed set in FixedSpeed1 (23.02).
CommandSel (10.01) = MainCtrlWord:
Use Inching1 [see MainCtrlWord (7.01)]
Acceleration and deceleration time for jogging is selected by JogAccTime (22.12) and JogDecTime
(22.13).
Int. Scaling: 1 == 1 Type: C Volatile: N
NotUsed
MCW Bit15
NotUsed
-
10.18 Jog2 (jogging 2 command)
Binary signal for
Jog2. Selects speed reference set in FixedSpeed2 (23.03):
Selections see
Jog1 (10.17).
Note
s:
See Jog1 (10.17).
Int. Scaling: 1 == 1 Type: C Volatile: N
NotUsed
MCW Bit15
NotUsed
-
10.19 - 10.20 Unused
10.21 MainContAck (main contactor acknowledge)
The drive trips with
F524 MainContAck [FaultWord2 (9.02) bit 7] if a digital input for the main contactor is
selected and the acknowledge is missing for 10 seconds
:
0 =
NotUsed
1 =
DI1 1= acknowledge OK, 0 = no acknowledge
2 =
DI2 1= acknowledge OK, 0 = no acknowledge
3 =
DI3 1= acknowledge OK, 0 = no acknowledge, default
4 =
DI4 1= acknowledge OK, 0 = no acknowledge
5 =
DI5 1= acknowledge OK, 0 = no acknowledge
6 =
DI6 1= acknowledge OK, 0 = no acknowledge
7 =
DI7 1= acknowledge OK, 0 = no acknowledge
8 =
DI8 1= acknowledge OK, 0 = no acknowledge
9 =
DI9 1= acknowledge OK, 0 = no acknowledge, only available with digital extension board
10 =
DI10 1= acknowledge OK, 0 = no acknowledge, only available with digital extension board
11 =
DI11 1= acknowledge OK, 0 = no acknowledge, only available with digital extension board
Note
:
The acknowledge is also dependent on the setting of
MainContCtrlMode (21.16).
Int. Scaling: 1 == 1 Type: C Volatile: N
NotUsed
DI11
DI3
-