Overview  DC Asterion Series 
3-52  M330460-01  Rev A 
3.9  Parallel and Series Operation 
Parallel and series modes of operation are used for applications requiring more current 
or voltage than is available from a single power supply. To meet the requirements for 
greater output current or voltage, up to five supplies could be connected in parallel, or 
up to two supplies could be connected in series. 
3.9.1  Parallel Operation 
In order to connect up to five power supplies in parallel, use a “Master/Slave” daisy-
chain wiring configuration as follows; refer to Figure 3-111: 
(There are two separate 9-pin connectors on the rear panel of each power supply, 
marked “PAR OUT” and “PAR IN”. Also, there are two separate 9-pin connectors on 
the rear panel of each power supply, marked ‘CAN OUT” and “CAN IN".) 
1.  Programming, readback, and control is performed through the Master. 
2.  Beginning with  the power  supply that is  to function  as the  Master,  use  an 
interface  cable  (890-524-01)  to  connect  the  PAR  OUT  connector  on  the 
designated Master power supply to the PAR IN connector on the second power 
supply (Slave 1). Repeat connection between Master CAN OUT and Slave 1 
CAN IN. 
3.  On the second power supply (Slave 1), use another interface cable to connect 
the PAR OUT connector to the PAR IN connector of the third power supply 
(Slave  2).  Continue  these  interconnections  up  to  a  maximum  of  5  power 
supplies. Repeat connection between Slave 1 CAN OUT and Slave 2 CAN IN. 
4.  Connect the Positive output terminals of all the power supplies and the load. 
5.  Connect the Negative output terminals of all the power supplies and the load.  
6.  Confirm that there are no shorts between the Positive and Negative output 
terminals. 
7.  Referring to Figure 3-111, connect twisted-pair sense cables as follows; ensure 
that all twisted-pair cables are as short as possible: 
All slave units shall have twisted-pair cables from their sense terminals to their own 
output terminals. 
For remote sense at the load, the master unit shall have a twisted-pair cable from its 
own sense terminals to the load terminals. 
For remote sense at the output terminals (local sense connection), the master unit 
shall have a twisted-pair cable from its own sense terminals to the output terminals of 
its own chassis. 
Note: The OVP circuit remains active for all units in parallel operation. If the units 
are set to different OVP levels, the paralleled system will trip according to the 
lowest  setting.  For  ease  of  use,  adjust  the  OVP  levels  for  the  slaves  to 
maximum and adjust the master OVP level to the desired setting.