Overview  DC Asterion Series 
2-10  M330460-01  Rev A 
 
Figure 2-5. AC Input Connector and Safety-Ground Stud 
 
A 1-Phase input is connected to terminals L1/L2 or L2/L3 (do not connect a 1-Phase 
input between L1/L3), while a 3-Phase input is connected to L1/L2/L3 (a connection to 
neutral is not utilized with 3-Phase input). The connector has compression terminals 
with female contacts. A ground connection must always be made to the utility earth 
protection ground using the AC Input connector pin or rear panel safety-ground stud. 
 
Line-1 input from utility AC mains;  
For 1-Phase input, connect lines to terminals L1 
and L2, or L2 and L3; or L1 and L3 
Line-2 input from utility AC mains.  
For 1-Phase input, connect lines to terminals L1 
and L2, or L2 and L3; or L1 and L3 
Line-3 input from utility AC mains;  
For 1-Phase input, connect lines to terminals L1 
and L2, or L2 and L3; or L1 and L3 
Safety-Ground connection from utility earth 
protection-ground. 
Table 2-2. AC Input Connector Pinout and Safety-Ground 
 
Chassis  connector  header:  Phoenix  P/N  1708514;  4-position,  compression 
terminals;  
Mating connector: Phoenix P/N 1709173; compression terminals; housing retained 
to header with screws;  
Wire stripping length: 10 mm (0.39”);  
Tightening torque: 0.7 Nm, min (6.1 lb-in) to 0.8 Nm, max (7 lb-in);  
Wire cross section: 0.2 mm2, min (24 AWG) to 10 mm2, max (8 AWG).  
Refer  to  Phoenix  P/N  1709173  manufacturer  datasheet  for  the  complete 
specifications of the Mating Connector.