Use the GND pin (G) provided in the input AC connector or the Stud provided in the 
rear panel for Safety-Ground Connection. For using the rear panel M4-0.7 x 7 stud, 
use nut tightening torque is 1.1 Nm (10 lb-in) max. 
CAUTION! 
To prevent damage to the AC input mating connector, follow torque specifications, 
and, if a wire ferrule is used, ensure that it is properly sized and that it has been 
crimped with the appropriate ferrule crimping tool. 
2.8.4  1-Phase AC Input Operation 
Connect the utility AC mains wires to the rear panel AC input connector terminals, 
L1/L2, L2/L3, or L1/L3. Ensure that the voltage does not exceed 264 VAC. The power 
source does not require a neutral connection, so the input could be between any two 
lines that have a voltage that does not exceed 264 VAC. Use wires with ratings equal 
to or greater than the current rating listed in the specification Section 1.2.2. A ground 
wire must be connected from the rear panel safety-ground terminal or the rear panel 
safety ground stud to the utility power earth protection-ground. 
2.8.5  3-Phase AC Input Operation 
Connect the utility AC source wires to the rear panel AC input connector terminals, 
L1/L2/L3; a neutral connection is not required. Ensure that the line-line voltage does 
not exceed 264 VAC. Use wires with ratings equal to or greater than the current rating 
listed in the specifications Section 1.2.2. A ground wire must be connected from the 
rear panel safety-ground terminal or the rear panel safety ground stud to the utility 
power distribution earth protection-ground. 
CAUTION! 
Do not connect an AC voltage that is greater than 264 VAC, either line-to-neutral 
or line-to-line, for 1-Phase or 3-Phase inputs. Exceeding the maximum AC input 
voltage could result in damage to the unit.