EasyManua.ls Logo

ATI Technologies QC-210 - 2 Installation; Module Installation

ATI Technologies QC-210
138 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual, Air Module, AH2
Document #9620-20-D-AH2-09
Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: info@ati-ia.com
D-3
2. Installation
The air modules are typically installed on the Tool Changers by ATI prior to shipment. The following steps outline
eld installation or removal as required. For detail information refer to Section 8—Drawings.
WARNING: Do not perform maintenance or repair(s) on the Tool Changer or modules unless
the Tool is safely supported or placed in the tool stand, all energized circuits (e.g. electrical,
air, water, etc.) are turned off, pressurized connections are purged and power is discharged
from circuits in accordance with the customers safety practices and policies. Injury or
equipment damage can occur with the Tool not placed and energized circuits on. Place the
Tool in the tool stand, turn off and discharge all energized circuits, purge all pressurized
connections, and verify all circuits are de-energized before performing maintenance or
repair(s) on the Tool Changer or modules.
WARNING: All pneumatic ttings and tubing must be capable of withstanding the repetitive
motions of the application without failing. The routing of electrical and pneumatic lines must
minimize the possibility of over stressing, pullout, or kinking the lines. Failure to do so can
cause critical electrical and/or pneumatic lines to malfunction and might result in injury to
personnel or damage to equipment.
CAUTION: Thread locker applied to fasteners must not be used more than once. Fasteners
might become loose and cause equipment damage. Always apply new thread locker when
reusing fasteners.
CAUTION: Air supply should be clean, dry, and non-lubricated. Supply pressure must not
exceed 100 psi and should be ltered minimum 40 micron. Connection lines must be properly
strain relieved.
2.1 Module Installation
Tools required: 5 mm Allen wrench (hex key), torque wrench
Supplies required: Clean rag, Loctite
®
242
1. Place the Tool in a secure location.
2. Uncouple the Master and Tool plates.
3. Turn off and de-energize all energized circuits (e.g. electrical, air, water, etc.).
4. Clean the mounting surface on the Tool Changer or Utility Coupler.
5. Place the module into the appropriate location on the Tool Changer or Utility Coupler body. Align the
module with the Tool Changer using the dowels in the bottom of the ledge feature.
6. Apply Loctite 242 to the supplied M6 socket head cap screws. Using a 5 mm Allen wrench, install the
(2) M6 socket head cap screws securing the module to the Tool Changer or Utility Coupler and tighten to
89 in-lbs (10.0 Nm).
7. Connect air plumbing to the module. Ensure that the connectors are clean.
8. After the procedure is complete, resume normal operation.

Table of Contents

Other manuals for ATI Technologies QC-210