Working with Protocol Focus 61 User Guide
9839 0211 01 Edition 2.0 104 (118)
7. On the lower-right corner of the Protocol management window, click Save.
13.1 Getting Result via Atlas Open Protocol
NOTE: Compatible Atlas Open Protocol (AOP): 1.6.3
By the message MID 0001 Communication start, an external application can start to
communicate via Atlas Open Protocol with the Focus 61. The reply (MID 0002) contains the basic
information about the controller.
Through the message MID 0060 Last tightening result data subscribe, it is
possible to make a subscription for all tightening results.
NOTE: It is MANDATORY to specify into the message MID 0060 the Station ID (0 or 1).
From the subscription, all the tightening results performed will be sent to the Atlas Open Protocol
application automatically by the message MID 0061.
NOTE: When the application does not want any further data from the Focus 61, it sends to the
controller the message MID 0063- Last tightening result data unsubscribe.
Atlas Open Protocol
First Step
MID 0001 Communication start
MID 0002
Second Step
Third
Step
MID 0060 Last tightening result data subscribe
MID 0061
Fourth Step
MID 0061
Fourth Step
•••••••••••••••
Fifth Step
MID 0063- Last tightening result data unsubscribe