This means that the router provides for example, information about the internal temperature
(OID 1.3.6.1.4.1.248.40.1.3.3) or about the power voltage (OID 1.3.6.1.4.1.248.40.1.3.4). For
binary inputs and output, the following range of OID is used:
OID Description
.1.3.6.1.4.1.30140.2.3.1.0 Binary input BIN0 (values 0,1)
.1.3.6.1.4.1.30140.2.3.2.0 Binary output OUT0 (values 0,1)
.1.3.6.1.4.1.30140.2.3.3.0 Binary input BIN1 (values 0,1)
Table 56: Object identifier for binary inputs and output
The list of available and supported OIDs and other details can be found in the application note
SNMP Object Identifier [8].
Figure 53: SNMP Configuration Example