EasyManua.ls Logo

Carrier Access Access Navigator - DSX-1 Cable Connections; Installation Summary; Precautions; Tools and Materials

Carrier Access Access Navigator
704 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-8 August 2003 Access Navigator - Release 1.8
Electrical Installation
DSX-1 Cable Connections
DSX-1 Cable Connections
Installation Summary
n Precautions ... 6-8
n Tools and Materials ... 6-9
n Prepare DSX-1 Cables ... 6-9
n Connect DSX-1 Cables to Access Navigator ... 6-11
n Attach Ferrite Beads ... 6-13
n Connect DSX-1 Cables to Interface or Patch Panel ... 6-14
Precautions
CAUTION! SHIELDED DSX-1 CABLES WITH FERRITE BEAD RF SUPPRESSORS ARE
REQUIRED FOR COMPLIANCE WITH NEBS 1089 EMI/EMC AND FCC REQUIREMENT
PART 15, TO PREVENT RADIO FREQUENCY INTERFERENCE WITH OTHER EQUIPMENT.
CAUTION! DSX-1 CABLES HAVE SOLID CONDUCTOR WIRES. IF ATTACHING RJ
TYPE CONNECTORS TO FLYING WIRE CABLES, BE SURE TO USE RJ CONNECTORS
DESIGNED FOR SOLID WIRE. USING RJ CONNECTORS DESIGNED FOR STRANDED WIRE
WILL CAUSE POOR SIGNAL CONNECTIONS AND SERVICE DISRUPTIONS.
WARNING! NEBS REQUIREMENT. DO NOT CONNECT THIS EQUIPMENT DIRECTLY
TO METALLIC TIP-AND-RING OUTSIDE PLANT CONDUCTORS. THIS EQUIPMENT CAN ONLY
BE USED FOR INTRA-BUILDING (INSIDE PLANT) INSTALLATION IN A CENTRAL OFFICE OR
CUSTOMER PREMISES.

Table of Contents