Cisco Catalyst Blade Switch 3120 for HP Command Reference
OL-12248-01
Chapter 2 Cisco Catalyst Blade Switch 3120 for HP Cisco IOS Commands
system env temperature threshold yellow
system env temperature threshold yellow
Use the system env temperature threshold yellow global configuration command on the switch stack
or on a standalone switch to configure the difference between the yellow and red temperature thresholds
that determines the value of yellow threshold. Use the no form of this command to return to the default
value.
system env temperature threshold yellow value
no system env temperature threshold yellow value
Syntax Description
Defaults These are the default values:
• Yellow—80°C
• Red—85°C
Command Modes Global configuration
Command History
Usage Guidelines You cannot configure the green and red thresholds but can configure the yellow threshold. Use the
system env temperature threshold yellow value global configuration command to specify the
difference between the yellow and red thresholds and to configure the yellow threshold. For example, if
the red threshold is 66 degrees C and you want to configure the yellow threshold as 51 degrees C, set the
difference between the thresholds as 15 by using the system env temperature threshold yellow 15
command.
Note The internal temperature sensor in the switch measures the internal system temperature and might vary
±5 degrees C.
Examples This example sets 15 as the difference between the yellow and red thresholds:
Switch(config)# system env temperature threshold yellow 15
Switch(config)#
Related Commands
value Specify the difference between the yellow and red threshold values (in Celsius). The
range is 10 to 25. The default value is 10.
Release Modification
12.2(40)EX This command was introduced.
Command Description
show env temperature status Displays the temperature status and threshold levels.