Protection Functions
PRS-7367 125
SYNC_25
U3P
ChkOK
DLDBOK
DLLBOK
LLDBOK
DdChkOK
VolDiffOK
FrDiffOK
AngDiffOK
Ux
Blk
SynChkBlk
DdChkBlk
SynChkOK
UsynVTSAlm
UsynPhsAlm
CB_Open
Figure 3.22-14 one shot for delay trip
For two-shot AR, the tripping command is received again after the second reclosing pulse is
issued, the reclosing shall be considered as unsuccessful and the blocked BO will be active. When
the next reclose command is issued, the last reclaim time will be end, the next progress will begin.
When AR is active, the 79AR_BlkInstTr BO is active until 79AR_Active is returned.