3.10.2 46N Protection Principle
The negative sequence current protection function can be enabled or disabled by setting the
corresponding 46N_Ena parameter values as "1" or "0".
The operation of the negative sequence current protection can be described using a module
diagram. All the modules in the diagram are explained in the next sections.
 Initiation element
The measured negative-sequence current is compared to the set 46N_Cur_Str value. If the
measured value exceeds the set 46N_Cur_Str, the level detector activates the timer module.
If the 46N_Ena_Mult input is active, the set 46N_Cur_Str, is multiplied by the set
46N_Mult_Cur_Str.