Protection Functions
PRS-7367 83
block the 46N_Str signals. The binary input 46N_Blk_Op can be used to block the 46N_Op
signals.
3.10.3 46N Application Scope
The negative sequence current quantities are not present during normal condition. The negative
sequence overcurrent protection elements can be set for faster and more sensitive operation than
the normal phase overcurrent protection for fault conditions occurring between two phases. The
negative sequence overcurrent protection also provides a back-up protection functionality for the
feeder earth-fault protection in solid and low resistance earthed networks.
3.10.4 46N Settings
Table 3.10-3 46N settings
3.11 Three-phase overvoltage protection 59
3.11.1 59 Overview
This relay provides a two-stage of overvoltage protection with definite time (DT) or inverse definite