MAN MACHINE INTERFACE
PRS-7367 303
7.3.6.2 Prot Settings
In this section user can change the different kind of information like public, measurement and
protection operation function settings etc. This section contains 01 to 11 pages and 42 parts of
relay settings. User can access this function through the following path: “Setting > Prot Settings”.
The detail of protection setting is listed in below figure 7.3.24:
/ Setting / Prot Settings
PUBLIC
Prot : 1000 A
0001 0001
Prot : 1 A
zeroSeq : 1000 A
zeroSeq : 1 A
Prot : 0110 kV
Prot : 100 A
SystemFr : 050.00
/ Setting / Prot Settings
MEA_CTRL
Vol_Dead_Zone : 0.50 %
0001 0005
Vol_Zero_Dead_Zone : 0.50 %
Cur_Dead_Zone : 0.50 %
Cur_Zero_Dead_Zone : 0.50 %
P_Dead_Zone : 0.50 %
P_Zero_Dead_Zone : 0.50 %
Q_Dead_Zone : 0.50 %
Q_Zero_Dead_Zone : 0.50 %
/ Setting / Prot Settings
OC_VEC
OC_Vol_Blk : 100.00V
0001 0001
OC_NegVol_Ena : 0
OC_NegVol_Blk : 057.00V
/ Setting / Prot Settings
OCTP_67P1
67P1_Dir_Mod : 0
0001 0002
67P1_Cur_Str : 020.00A
67P1_RCA : 090
O
67P1_Mul_Cur : 01.0
67P1_Curve_paraA : 000.00s
67P1_Curve_paraB : 000.00s
67P1_Curve_paraC : 1.00
67P1_Curve_paraP : 2.00
(a) (b)
(d)(c)
Figure 7.3-24 Diagram of Protection Setting
7.3.7 Configuration Information
This section divided into two sub-function like time and authorization. In this part user can set the
device date and time according to the time zone of certain country. Besides that, the monitoring
and controlling authorization of different users (of different post) can also be modified. The
diagram of configuration information is shown in below figure 7.3.25.