Protection Functions
PRS-7367 163
3.33.2 CB Position
Table 3.33-2 Input Signals
NO.
Signal
CB_Opn
CB Close input
CB_Cls
CB Open input
Table 3.33-3 Output signal
NO.
Signal
Err
CB positon is error, when CB Open input and CB Close input are 1 or 0.
Opn
CB Open
Cls
CB Close
Table 3.33-4 Settings
No
Name
Range
Unit
Step
Defa
ult
Description
1
CB_DPS_Set
0~3
-
1
0
Double signal setting:
Only for CB connected in the
configuration at the same time CB_Opn
and CB_Cls terminal, when CB_Opn
and CB_Cls are both 1 or 0, Err=1,
Opn=0,Cls=0.
=0,Opn= CB_Opn,Cls = CB_Cls,
=1,Opn= CB_Opn,Cls =Not(CB_Opn);
=2,Cls = CB_Cls,Opn =Not(CB_Cls);
=3,Opn= CB_Opn 且 Not(CB_ Cls),Cls =
CB_ Cls and Not(CB_Opn)
Notes:
1) If only configuring CB_Opn, Opn=
CB_Opn,Cls =Not(CB_Opn);
2) If only configuring CB_ Cls,Cls =
CB_ Cls,Opn =Not(CB_ Opn);
3.34 Backup power automatic switch
3.34.1 Overview
Backup power automatic switching mainly applies to circumstances where single-busbar
stage of single-ended substation, for example, stage backup power automatic switching at load
side of main transformer and bridge backup power automatic switching at power supply side.