Protection Functions
PRS-7367 187
3.37.4 Settings
In the following table, i is the protection stage number, it can be set according to the requirements.
Name
Values
(Range)
Unit
Step
Default
Description
OCR_INRi_Ena
0 - 1
-
1
0
0: Disable
1: Enable
OCR_INRi_HarmCoe
0.05-1
s
0.001
0.2
The ratio setting for second
Harmonic Current to
fundamental current
OCR_INRi_Op_T
0.02 - 60.00
s
0.01
0.02
Operate time delay
OCR_INRi_Reset_T
0 - 60.00
s
0.01
0.02
Reset time delay