EasyManua.ls Logo

CYG PRS-7367 - Binary Input Module

CYG PRS-7367
360 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware
PRS-7367 275
Name
Description
UL1
The phase voltage inputs of line for protection and metering.
UL1n
UL2
The phase voltage inputs of line for protection and metering.
UL2n
Ia
The three phase current inputs .
Ia’
Ib
Ib’
Ic
Ic’
I1
The phase current inputs of line1.
I1’
I2
The phase current inputs of line2.
I2’
I3
The phase current inputs of line3.
I3’
I4
The phase current inputs of line4.
I4’
6.6 Binary Input Module
The BI module contains 18 binary inputs, the optical isolated input terminals, which can perform
different monitoring functions, such as detecting the breaker and switch positions of the
corresponding bay. All the BI terminals can be used as general purpose binary inputs or special
purpose (protection function or control function) binary inputs. For example, the general purpose
binary inputs can be used to indicate the status (0 for normal condition and 1 for abnormal
condition) of a certain apparatus. For another example, the special purpose binary inputs can be
used to acting as the blocking or start signal for a certain protection function.
All the binary inputs can be visually and flexibly configured through the PRS IED Studio
configuration tool, which determine what information do they transmit between the CPU module
and BI module.
The frame of the BI module terminal is described as below.