EasyManuals Logo

CYG PRS-7367 User Manual

CYG PRS-7367
360 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #222 background imageLoading...
Page #222 background image
Protection Functions
214 PRS-7367
1
LNP_PE_Phi_Shift
0, 15 or 30
deg
15
0
0:Line Length≥40KM;
15: 40KM>Line Length≥10KM;
30: 10KM>Line Length;
Line Length is 21FL_LineLen
2
LNP_ResCur_Str
0.02-20.00In
A
0.01In
0.05In
Line Residual current start value
3
LNP_PDIR_MOD
0~2
-
1
0
The FPS Directional mode:0-2 for
"Non-directional", "Forward" or
"Reverse"
4
LNP_PRCA
0 - 360
°
1
45
The FPS Characteristic angle
3.46 Stabilized differential protection for machines 87MPDIF
3.46.1 Overview
For machines (motor or generator) above 2MW, or when the capacity is 2MW but the sensitivity
of fast overcurrent protection is insufficient, stable differential protection should be used. Stable
differential protection is used as the main protection for machines in case of phase to phase short
circuits. The CT of ordinary current stable differential protection can be installed at the switch
cabinet outlet of the power supply cable, and the protection range can include the power supply
cable of the machines.
3.46.1.1 Function Block
87MP_DIF
ID3P
Str
Op
Op_A
Op_B
Op_C
Block
Blk_OpHS
Blk_OpLS
CT Sta
Op_HS
Op_LS
Alm
CT Blk
Blkd
Blkd_A
Blkd_B
Blkd_C
Figure 3.46-1 Function block
3.46.1.2 Signals
Table 3.46-1 Input signal
Signal
Description
ID3P
The differential and biased current, including Ida, Idb, Idc, Ira, Irb,
Irc

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CYG PRS-7367 and is the answer not in the manual?

CYG PRS-7367 Specifications

General IconGeneral
BrandCYG
ModelPRS-7367
CategoryControl Unit
LanguageEnglish