EasyManua.ls Logo

CYG PRS-7367 - System parameter

CYG PRS-7367
360 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Protection Functions
34 PRS-7367
Category
Profession Vocabulary
Abbreviation
Energize
Energ
Weigh
Weig
Activation / Activate
Activ
Error
Err
Configuration
Cfg
Parameter
Para
Management
Mana
Interrupt
Intr
SelfCheck
SelfChk
Start
Str
Apparatus
Generator
Gen
Motor
Motor
Rotor
Rotor
Stator
Stator
Busbar
Bus
Transformer
TF
Transmission Line
TL
Line
Line
Capacitor
Cap
Reactor
Reac
Resistor
Resis
Switch
Sw
Component
Comp
3.1.2 System parameter
No
Name
Range
Unit
Step
Typical
Description
1
Prot_TA_Primary
1-9999
A
1
1000
The rated primary value of the
No.1 protection phase CT
2
Prot_TA_Secondary
1-5
A
4
5
The rated secondary value of the
No.1 protection phase CT
3
ZeroSeq_TA_Primary
1-9999
A
1
1000
The rated primary value of the
No.1 zero sequence CT
4
ZeroSeq_TA_Second
ary
1-5
A
4
5
The rated secondary value of the
No.1 zero sequence CT
5
Prot_TV_Primary
0.01~1000
kV
0.01
110
The rated primary value of the
No.1 protection VT
6
Prot_TV_Secondary
0.01~1000
V
0.01
115
The rated secondary value of the
No.1 protection VT
7
Prot2_TA_Primary
1-9999
A
1
1000
The rated primary value of the
No.2 protection phase CT
8
Prot2_TA_Secondary
1-5
A
4
5
The rated secondary value of the
No.2 protection phase CT

Table of Contents