Protection Functions
PRS-7367 51
3.4.2.2 50G
The principle is same as the 51G except 50G time delay is instantaneous.
&
FLG
Initiation
50G_Str
SIG
50G_Op
SIG
SIG
50G_Blk=1
SIG
50G_Blk_Str=1
SIG
50G_Blk_Op=1
&
&
& 50G_Alm
SIG
50G_Alm_Ena=1
SET
&
3ms
50G_Op_T
Figure 3.4-4 Functional module diagram for 50G
3.4.2.3 51GVT
The principle is same as the 51G except 51GTV is just only enabled when VTS alarm.
&
51GVT_Ena=1
SET
Io>Set Value
ANA
Initiation
FLG
SIG
PTSAlm
Figure 3.4-5 The Initiation logic diagram for 51GVT
3.4.3 51G Application Scope
51G is designed for protection and clearance of earth faults in distribution and sub-transmission
networks, especially when the neutral point is isolated or earthed via a resonance coil or through
low resistance. It also applies to solidly earthed networks and earth-fault protection of different
equipment connected to the power systems, such as shunt capacitor bank or shunt reactors and
for backup earth-fault protection of power transformers.
3.4.4 51G Settings
In the following table, i is the protection stage number, it can be set according to the requirements.
Table 3.4-3 50G settings
No.
Name
Values(Range)
Unit
Step
Default
Description
1
50Gi_Cur_Str
0.02-20.00In
A
0.01In
0.04In
The Stage i Start value
2
50Gi_Mul_Cur
0.8 - 10.0
-
0.1
1
The Stage i Multiplier for scaling
the start value
8
50Gi_Op_T
0.0-0.200
s
0.001
0.000
The Stage i Operating time for
IDMT
9
50Gi_Reset_T
0.000 -60.000
s
0.001
0.02
The Stage i Reset delay time
10
50Gi_Ena
0~1
-
1
0
The Stage i Operation