Protection Functions
PRS-7367 193
Selection of time delay curve type:
=0: definite
=1: IDMT
Time multiplier for Wattmetric
IDMT curves
Operate delay time for definite
time
PTs alarm blocking enable
3.39 Under Current Protection 37C
3.39.1 Overview
This relay provides one stage under current protection for monitoring a motor or capacitor.
3.39.1.1 Function Block
The function block of the protection is as below.
I3P
UCR_37C
Blk
BlkStr
BlkOp
Str
Op
BI52a
3.39.1.2 Signals
Table 3.39-1 Input Signals
The current magnitude in all the three phases
This signal blocks all the binary output signals of the function
This signal blocks all the start outputs of the function
This signal blocks all the trip signals of the function.
The binary input from the auxiliary normally opened contact of
circuit breaker
Table 3.39-2 Output Signals