Protection Functions
PRS-7367 135
=0
=1
Set Value = 51NA_Cur_Str
Set Value =51NA_Cur_Str
*51NA_Mul_Cur
&
51NA_Ena=1SET
Ia2>Set ValueANA
Initiation
FLG
SIG 51NA_ENA_MULT
Figure 3.24-3 Initiation module diagram
The measured neutral unbalance current is compared to the set 51NA_Cur_Str. If the measured
value exceeds the set 51NA_Cur_Str and no block signal is activated, the timer and 51NA_Str
signal are activated. If the 51NA_Ena_Mult input is active, the 51NA_Cur_Str value setting is
multiplied by the 51NA_Mult_Cur setting.
Where:
51NA_Ena_Mult is a binary input to enable or disable the start multiplier.
51NA_Ena is used to enable or disable the protection.
51NA_Cur_Str is the start value.
51NA_Mult_Cur is the multiplier for scaling the start value.
NOTICE!
Do not set the multiplier setting 51NA_Mult_Cur higher than necessary. If the value is
too high, the function may not operate at all during an inrush followed by a fault, no
matter how severe the fault is.
The start value multiplication is normally done when the inrush detection function
(OCR_INR) is connected to the Ena_Mult input by Three phase inrush function
OCR_INR.
3.24.2.2 Timer element
The functional module diagram is shown as below:
&
Timer
FLG
Initiation
51NA_STR
SIG
51NA_OP
SIG
SIG
51NA_BLK=1
SIG
51NA_BLK_STR=1
SIG
51NA_BLK_OP=1
&
&
Figure 3.24-4 Functional module diagram