EasyManua.ls Logo

CYG PRS-7367 - Page 151

CYG PRS-7367
360 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Protection Functions
PRS-7367 143
Figure 3.26-2 The neutral balance voltage of Double-Y-connected capacitor bank
3.26.2.1 Initiation logic
The initiation of neutral voltage unbalance protection can be described by using a module diagram.
The functional module diagram is shown as below: the unbalance voltage U_UNB is sampled in
device by Ua2.
&
Ua2>59NA_Vol_Str
ANA
SIG
59NA_Blk=1
59NA_Ena=1
SET
Initiation
FLG
Figure 3.26-3 The initiation diagram
The measured neutral unbalance voltage is compared to the set 59NA_Vol_Str. If the measured
value exceeds the set 59NA_Vol_Str and no block signal is activated, the timer and 59NA_Str
signal are activated.
Where:
59NA_Ena is used to enable or disable the protection.
59NA_Vol_Str is the start value.
3.26.2.2 Timer element
The functional module diagram is shown as below:

Table of Contents