Protection Functions
PRS-7367 169
&
ANA
IL1 > L1_Live_Cur
SIG
CB01_Open
3ms
10s
SIG
CB01_Pos_Err
&
ANA
IL2 > L2_Live_Cur
SIG
CB02_Open
3ms
10s
SIG
CB02_Pos_Err
&
SIG
CB03_Open
3ms
10s
SIG
CB03_Pos_Err
ANA
Ia > I_Cur_Str
ANA
Ib > I_Cur_Str
ANA
Ic >I_Cur_Str
1
Figure 3.34-7 Diagram of CB position error logic
5) The time period during which backup power supply doesn’t meet live voltage condition is
longer than 15s;
6) Backup breaker is not in backup status, that means backup breaker has been closed;
7) Operating breaker fails to trip or backup breaker fails to close;
Charge Conditions
The logic diagrams of the charge condition of BPAS1 is shown in Figure 3.34-8.
0ms
15s
&
&
1
&
&
SIG
BPAS1_Chg_Ok
BPAS1_Ena=1
SET
BPAS1_DisCharge
SIG
CB01_Open
CB02_Open
CB03_Open
CB_Aft_Cls_Ena=0
SET
CB01_Aft_Cls
CB03_Aft_Cls
AND_Bus1_Live_Vol
AND_Bus2_Live_Vol
SIG
SIG
SIG
SIG
SIG
SIG
SIG
SIG
BPAS_Ena
SIG
1
L2_Vol_Ena=0
SET
L2_Live_Vol
SIG
Figure 3.34-8 Diagram of the charge condition of BPAS1
The charge conditions of BPAS1 and BPAS2 are similar, so take BPAS1 for example.
The charge conditions of BPAS1 cover the following items:
1) No blocking condition, discharge condition;