Protection Functions
184 PRS-7367
The closing BO last for at least 100ms
The return condition: using “AND” logic with the closing relay return with no current or CB
close position
The closing BO will return after the return condition is ok and last for the Closei_OffDelay
setting.
When CB Close is used, all condition is ok but the CB Close is still not 1, the closing BO
will return after 1s.
Ia>0.05In
ANA
Ib>0.05In
ANA
Ic>0.05In
ANA
1
FLGCurrent
Figure 3.36-2 The No current condition
CloseClear
FLG
SIG CloseIn
SIGCloseOut
&
1
SET
ModeOutput=1
&
&
SIGLockOut
1
OnDelay / 0
SIG CloseOut
0 / 100ms
Figure 3.36-3 The closing and Lockout BO
SET
ModeOutput=0
Current
FLG
1
SIG CB_Cls
1
OffDelay / 0
&
SIG CloseOut
1S / 0
SET
ModeOutput=1
SIG CloseIn
SIG CloseIn
&
1
FLGCloseClear
SIG Reset
Figure 3.36-4 The closing BO return