are the current and voltage of the Self-polarizing. RCA
is the Relay characteristic angle, which is used to turn the direction element to best comply with
the fault situation.
The directionality of the operation can be selected with the 67G_Dir_Mod setting. The user can
select either "Non-directional", "Forward" or "Reverse" operation.
The directionality also can be use in double circuit line by negative current and voltage, it can be
enable or disable by setting 67G1_PolU, when 67G1_PolU=1, the condition is following:
Self-polarizing is used (I
2
-(-U
2
)) to determine the fault direction.
The evaluation of the forward directionality is according to the equation:
Figure 3.5-3 The voltage control logic diagram
PTS Alarm Blocking of 67G
The PTS alarm can be set by PTS_Blk setting, if PTS_Blk=1 and the PTS Alm signal is 1, the 67G