Application Guide | iC2-Micro Frequency Converters
Selection number Selection name Selection description
3 Trip Lock Alarm is set to trip lock.
4 Trip with Delayed Reset Alarm is configured into trip alarm, which can be reset after a
delay time. For example, if Fault 13, Overcurrent is configured
to this option, it can be reset 3 minutes after the alarm. This
option uses the 8th element to control the fault level of Fault 13,
Overcurrent.
5 Fly start At start-up, the frequency converter tries to catch a spinning
motor. If this option is selected, P 5.6.3 Enable Flying Start is
forced to [1] Enabled. This option uses the 8th element to control
the fault level of Fault 13, Overcurrent.
Table 64: Selection of Action when Selected Alarm Appears
Index Alarm Trip lock Trip with delay Fly start
0 Reserved – – –
1 Reserved – – –
2 Reserved – – –
3 Reserved – – –
4 Reserved – – –
5 Reserved – – –
6 Reserved – – –
7 Overcurrent D X X
D indicates Default Setting and X indicates Possible Selection.
P 4.6.14 Sync. Locked Rotor Protection
Locked rotor detection for PM motor.
Default value: 0 [Off] Parameter type: Selection
Parameter
number:
3022 Unit: –
Data type: enum Access type: Read/Write
Selection number Selection name Selection description
0 Off The function is not active.
1 On The locked rotor protection for PM motors.
P 4.6.15 Sync. Locked Rotor Detection Time [s]
Locked rotor detection time for PM motor.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 141