Application Guide | iC2-Micro Frequency Converters
Parameter
number:
2262 Unit: s
Data type: uint16 Access type: Read/Write
P 5.2.16 Watchdog Response
Use this parameter to select the timeout function. The timeout function activates when the control word fails to be updated within the
time period specified in P 5.2.17 Watchdog Delay.
Default value: 0 [Off] Parameter type: Selection
Parameter
number:
804 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 Off
1 Freeze Output
2 Stop
3 Jogging
4 Max. Speed
5 Stop and Trip
6 Qstop and Trip
7 Select Setup 1
8 Select Setup 2
26 Trip
P 5.2.17 Watchdog Delay
Use this parameter to enter the maximum time expected to pass between the reception of 2 consecutive telegrams. If this time is
exceeded, it indicates that the serial communication has stopped, and the function selected in P 5.2.16 Watchdog Response is then
carried out.
Default value: 1.0 Parameter type: Range (0.5–6000.0)
Parameter
number:
803 Unit: s
Data type: uint16 Access type: Read/Write
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 147