Application Guide | iC2-Micro Frequency Converters
P 5.6.2 Start Function
Use this parameter to select the start function during start delay, in case a non-zero value is set in P 5.6.1 Start Zero Speed Time.
Default value: 2 [Coast/delay time] Parameter type: Selection
Parameter
number:
172 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 DC Hold/delay time Energize motor with a DC hold current (P 5.7.6 DC Hold Current
%) during the start delay time.
1 DC-Brake/delay time Energize motor with a DC break current (P 5.7.4 DC Brake Current
%) during the start delay time.
2 Coast/delay time Motor coasted during the start delay time (inverter off).
3 Start speed clockwise Only possible with VVC+. Regardless of the value applied by
the reference signal, the output speed applies the setting of the
start speed in P 5.6.4 Start Speed [Hz] and the output current
corresponds to the setting of the start current in P 5.6.5 Start
Current. This function is typically used in hoisting applications
without counterweight and especially in applications with a
cone-motor, where the start is clockwise, followed by rotation in
the reference direction.
4 Horizontal operation Only possible with VVC+. For obtaining the function described
in P 5.6.4 Start Speed [Hz] and P 5.6.5 Start Current during the
start delay time. The motor rotates in the reference direction. If
the reference signal equals 0, P 5.6.4 Start Speed [Hz] is ignored
and the output speed equals 0. The output current corresponds
to the setting of the start current in P 5.6.5 Start Current.
5 VVC+ clockwise The start current is calculated automatically. This function uses
the start speed in the start delay time only.
P 5.6.3 Enable Flying Start
Use this parameter to control the flying start function. This function makes it possible to catch a motor which is spinning freely due to a
mains dropout.
Default value: 0 [Disabled] Parameter type: Selection
Parameter
number:
173 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 165