Application Guide | iC2-Micro Frequency Converters
NOTICE
Sleep mode is not active when local reference is active (set speed manually with navigation buttons on the control panel). Does
not work in Local mode. Remote setup in open loop must be carried out before setting input/output in closed loop.
P 5.12.7.1 Sleep Mode in Process Closed-loop Mode
This parameter is for sleep mode running in process closed loop. Use this parameter to set whether the feedback is detected for entering
sleep mode.
Default value: 0 Parameter type: Selection
Parameter
number:
2202 Unit: –
Data type: enum Access type: Read/Write
Selection number Selection name Selection description
0 Feed. and Speed Feedback is detected together with the speed.
1 Speed Feedback is not detected, only sleep speed and time are
checked.
2 Feedback Feedback is detected only.
P 5.12.7.2 Minimum Run Time
Set the minimum running time for the motor after a start command (digital input or bus) before entering the sleep mode.
Default value: 10 Parameter type: Range (0–600)
Parameter
number:
2240 Unit: s
Data type: uint16 Access type: Read/Write
P 5.12.7.3 Minimum Sleep Time
Set the minimum time for staying in sleep mode. This setting overrides any wake-up conditions.
Default value: 10 Parameter type: Range (0–600)
Parameter
number:
2241 Unit: s
Data type: uint16 Access type: Read/Write
P 5.12.7.4 Wake-Up Speed [Hz]
This parameter is used when P 5.4.2 Operation Mode is set for open loop, and the speed reference is from an external controller. Set the
reference speed when the Sleep Mode is deactivated.
Default value: 100 Parameter type: Range (0–4000)
Parameter
number:
2243 Unit: Hz
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 183