Default value: 0 [PNP] Parameter type: Selection
Parameter
number:
500 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 PNP Action on positive directional pulses (0). PNP systems are pulled
down to ground (GND).
1 NPN Action on negative directional pulses (1). NPN systems are pulled
up to +24 V internally in the frequency converter.
P 9.4.1.2 T13 Digital Input
Select the function from the available digital input range.
Default value: 8 [Start] Parameter type: Selection
Parameter
number:
510 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 No Operation No reaction to signals transmitted to the terminal.
1 Reset Resets the frequency converter after a trip/alarm. Not all alarms
can be reset.
2 Coast Inverse Coasting stop, inverted input (NC). The frequency converter
leaves the motor in free mode. Logic 0⇒coasting stop.
3 Coast and Reset Inverse Reset and coasting stop inverted input (NC). Leaves motor in free
mode and resets frequency converter. Logic 0⇒coasting stop.
Logic 1 to Logic 0⇒reset.
4 Quick Stop Inverse Inverted input (NC). Generates a stop in accordance with the
quick stop ramp time set in P 5.7.7 Quick Stop Ramp Time. When
the motor stops, the shaft is in free mode. Logic 0⇒Quick-stop.
5 DC-brake Inverse Inverted input for DC braking (NC). Stops the motor by
energizing it with a DC current for a certain time period. See P
5.7.4 DC Brake Current % to P 5.7.5 DC Brake Frequency. The
function is only active when the value in P 5.7.3 DC Brake Time is
different from 0. Logic 0⇒DC braking.
220 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters