Selection number Selection name Selection description
0 Input Defines terminal 15 as a digital input.
1 Output Defines terminal 15 as a digital output.
P 9.4.2.2 T15 Digital Output
Select the function to control the digital output.
Default value: 0 [No Operation] Parameter type: Selection
Parameter
number:
530 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 No Operation Default for all digital outputs.
1 Control Ready The control card is ready.
2 Drive Ready The frequency converter is ready for operation and applies a
supply signal on the control board.
3 Drive Ready / Remote Mode The frequency converter is ready for operation and is in Remote
mode.
4 Stand-by / No Warning Ready for operation. No start or stop command is given (start/
disable). No warnings are active.
5 Running The motor is running and shaft torque is present.
6 Running / No Warning The motor is running and there are no warnings.
7 Run in Range / No Warning The motor is running within the programmed current and speed
ranges set in P 4.6.4 Warning Current Low to P 4.6.3 Warning
Current High. There are no warnings.
8 Run on Ref. / No Warning The motor runs at reference speed. No warnings.
9 Fault A fault activates the output.
10 Fault or Warning A fault or a warning activates the output.
11 At Torque Limit The torque limit set in P 5.10.1 Motor Torque Limit or P 5.10.2
Regenerative Torque Limit has been exceeded.
12 Out of Current Range The motor current is outside the range set in P 2.7.1 Output
Current Limit %.
13 Below Current, Low The motor current is lower than set in P 4.6.4 Warning Current
Low.
14 Above Current, High The motor current is higher than set in P 4.6.3 Warning Current
High.