Selection number Selection name Selection description
41 Below Reference, Low This option is active when the actual speed is below the speed
reference setting.
42 Above Refefence, High This option is active when the actual speed is above the speed
reference setting.
45 Bus Control Control output via fieldbus. The state of the output is set in P
9.4.6.1 Digital & Relay Bus Control. The output state is retained in
the event of fieldbus timeout.
46 Bus Control, Timeout: On Control output via fieldbus. The state of the output is set in P
9.4.6.1 Digital & Relay Bus Control. When bus timeout occurs, the
output state is set high (On).
47 Bus Control, Timeout: Off Control output via fieldbus. The state of the output is set in P
9.4.6.1 Digital & Relay Bus Control. When bus timeout occurs, the
output state is set low (Off).
55 Pulse Output Use terminal 15 as pulse output.
56 Heat Sink Cleaning Warning, High Activated when the heat sink temperature is not lower than the
calculated value. The calculated value is equal to the maximum
value of P 2.1.9 Heat Sink Temperature minus the current value of
P 2.1.9 Heat Sink Temperature.
60 Comparator 0 Use result of comparator 0 in logic rule.
61 Comparator 1 Use result of comparator 1 in logic rule.
62 Comparator 2 Use result of comparator 2 in logic rule.
63 Comparator 3 Use result of comparator 3 in logic rule.
64 Comparator 4 Use result of comparator 4 in logic rule.
65 Comparator 5 Use result of comparator 5 in logic rule.
70 Logic rule 0 Use result of logic rule 0 in logic rule.
71 Logic rule 1 Use result of logic rule 1 in logic rule.
72 Logic rule 2 Use result of logic rule 2 in logic rule.
73 Logic rule 3 Use result of logic rule 3 in logic rule.
74 Logic rule 4 Use result of logic rule 4 in logic rule.
75 Logic rule 5 Use result of logic rule 5 in logic rule.
80 SL digital output A See P 8.4.6.2 Action. The output goes high whenever the smart
logic action [38] Set digital out A high is executed. The output
goes low whenever the smart logic action [32] Set digital out A
low is executed.
81 SL digital output B See P 8.4.6.2 Action. The output goes high whenever the smart
logic action [39] Set digital out B high is executed. The output
goes low whenever the smart logic action [33] Set digital out B
low is executed.
160 No Fault The output is high when no alarm is present.
238 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters