Selection number Selection name Selection description
0 No Operation Default for all digital outputs.
1 Control Ready The control card is ready.
2 Drive Ready The frequency converter is ready for operation and applies a
supply signal on the control board.
3 Drive Ready / Remote Mode The frequency converter is ready for operation and is in Remote
mode.
4 Stand-by / No Warning Ready for operation. No start or stop command is given (start/
disable). No warnings are active.
5 Running The motor is running and shaft torque is present.
6 Running / No Warning The motor is running and there are no warnings.
7 Run in Range / No Warning The motor is running within the programmed current and speed
ranges set in P 4.6.4 Warning Current Low to P 4.6.3 Warning
Current High. There are no warnings.
8 Run on Ref. / No Warning The motor runs at reference speed. No warnings.
9 Fault A fault activates the output.
10 Fault or Warning A fault or a warning activates the output.
11 At Torque Limit The torque limit set in P 5.10.1 Motor Torque Limit or P 5.10.2
Regenerative Torque Limit has been exceeded.
12 Out of Current Range The motor current is outside the range set inP 2.7.1 Output
Current Limit %.
13 Below Current, Low The motor current is lower than set in P 4.6.4 Warning Current
Low.
14 Above Current, High The motor current is higher than set in P 4.6.3 Warning Current
High.
15 Out of Frequency Range Output frequency is outside the frequency range.
16 Below Frequency, Low The output speed is lower than the setting inP 4.6.2 Warning
Freq. Low.
17 Above Frequency, High The output speed is higher than the setting in P 4.6.1 Warning
Freq. High.
18 Out of Feedback Range The feedback is outside the range set in P 5.2.4 Warning
Feedback Low andP 5.2.3 Warning Feedback High.
19 Below Feedback, Low The feedback is below the limit set in P 5.2.4 Warning Feedback
Low.
20 Above Feedback, High The feedback is above the limit set in P 5.2.3 Warning Feedback
High.
21 Thermal Warning The thermal warning turns on when the temperature exceeds
the limit in the motor, the frequency converter, the brake resistor,
or the thermistor.
240 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters