Application Guide | iC2-Micro Frequency Converters
P 9.4.3.2 Relay ON-Delay
Enter the delay of the relay cut-in time.
Default value: 0.01 Parameter type: Range (0.00–600.00)
Parameter
number:
541 Unit: s
Data type: uint16 Access type: Read/Write
Selected
event
Relay
output
Selected
event
Relay
output
P 9.4.3.2 Relay
ON-Delay
P 9.4.3.2 Relay
ON-Delay
P 9.4.3.3 Relay
OFF-Delay
e30bk137.10
Figure 82: On Delay, Relay
P 9.4.3.3 Relay OFF-Delay
Enter the delay of the relay cut-out time. See P 9.4.3.1 Function Relay. If the selected-event condition changes before a delay timer
expires, the relay output is unaffected.
Default value: 0.01 Parameter type: Range (0.00–600.00)
Parameter
number:
542 Unit: s
Data type: uint16 Access type: Read/Write
Selected
event
Relay
output
e30bk138.10
P 9.4.3.2 Relay
ON-Delay
P 9.4.3.3 Relay
OFF-Delay
Figure 83: Off Delay, Relay