Parameters
130BB927.10
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
4 - 20mA
+
-
Function Setting
6-12 Terminal 53
Low Current
4 mA*
6-13 Terminal 53
High Current
20 mA*
6-14 Terminal 53
Low Ref./Feedb.
Value
0 RPM
6-15 Terminal 53
High Ref./Feedb.
Value
1500 RPM
* = Default value
Notes/comments:
D IN 37 is an option.
Table 4.11 Analog Speed Reference (Current)
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
5kΩ
130BB683.10
Function Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
High Voltage
10 V*
6-14 Terminal 53
Low Ref./Feedb.
Value
0 RPM
6-15 Terminal 53
High Ref./Feedb.
Value
1500 RPM
* = Default value
Notes/comments:
D IN 37 is an option.
Table 4.12 Speed Reference (using a Manual Potentiometer)
4.3.11
Run/Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB680.10
Function Setting
5-10 Terminal 18
Digital Input
[8] Start*
5-12 Terminal 27
Digital Input
[7] External
interlock
* = Default value
Notes/comments:
D IN 37 is an option.
Table 4.13 Run/Stop Command with External Interlock
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB681.10
Function Setting
5-10 Terminal 18
Digital Input
[8] Start*
5-12 Terminal 27
Digital Input
[7] External
interlock
* = Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] no
operation, a jumper wire to
terminal 27 is not needed.
D IN 37 is an option.
Table 4.14 Run/Stop Command without External Interlock
Application Examples
Design Guide
MG20N622 Danfoss A/S © 09/2014 All rights reserved. 113
4 4

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals