Enclosure Sizes C, T6
60° AVM – Pulse Width Modulation
1 2 4
6 8
20%
10
40%
60%
80%
90%
100%
o
50 C
o
45 C
110%
f
sw
(kHz)
0
0
(%)
l
out
C1 & C2
NO
130BB821.10
Figure 5.19 Output Current Derating with Switching Frequency
and Ambient Temperature for 600 V Adjustable Frequency
Drives, Enclosure Sizes C, 60 AVM, NO
SFAVM – Stator Frequency Asyncronous Vector
Modulation
1 2 4
6 8
20%
10
40%
60%
80%
90%
100%
o
50 C
o
45 C
110%
f
sw
(kHz)
0
0
(%)
l
out
C1 & C2
NO
130BB827.10
Figure 5.20 Output Current Derating with Switching Frequency
and Ambient Temperature for 600 V Adjustable Frequency
Drives, Enclosure Sizes C; SFAVM, NO
Enclosure Size C, T7
60° AVM – Pulse Width Modulation
f
sw
(kHz)
130BB213.11
20.4
34
I
out
(A)
28.9
1 2 64
55°C
50°C
45°C
8 10
C2 all options
13.6
27.2
Figure 5.21 Output Current Derating with Switching Frequency
and Ambient Temperature for Enclosure Size C2, 60° AVM.
SFAVM – Stator Frequency Asyncronous Vector
Modulation
f
sw
(kHz)
130BB214.10
40
60
80
100
I
out
(A)
86.6
1 2 64
55°C
50°C
45°C
8 10
C2 all options
66.6
20
Figure 5.22 Output Current Derating with Switching Frequency
and Ambient Temperature for Enclosure Size C2, SFAVM.
2
20%
4 6 8 10
40%
60%
80%
100%
110%
I
out
(%)
f
sw
(kHz)
I
LOAD
at T
AMB
max
130BD597.10
0
0
I
LOAD
at T
AMB
max +5 °C
I
LOAD
at T
AMB
max +5 °C
Figure 5.23 Output Current Derating with Switching Frequency
and Ambient Temperature for Enclosure Size C3
Special Conditions
VLT
®
AQUA Drive FC 202
120 Danfoss A/S © 09/2014 All rights reserved. MG20N622