FC 202 Horizontal braking 10% duty cycle
Adjustable frequency drive data
Brake resistor data Installation
R
rec
[Ω]
P
br,cont.
[kW (hp)]
Danfoss part number Cable
cross-
section
[mm
2
(AWG)]
Thermo
relay
[A]
Line
power
type
P
m
[kW
(hp)]
R
min
[Ω]
R
br,nom
[Ω]
Wire IP54
Screw
terminal
IP21
Screw
terminal
IP65
Bolt
connection
IP20
T4
160
(225)
2.5 3.6 3.3
13.000
(17.426)
- - - 175u3084 35 (2) 63
T4
200
(275)
2.0 2.9 2.7
16.000
(21.448)
- - - 175u3088 50 (1/0) 77
T4
250
(350)
1.6 2.3 2.1
20.000
(26.809)
- - - 175u3091 70 (3/0) 98
T4
315
(425)
1.2 1.8 1.7
26.000
(34.853)
- - - 175u3093
2 x 35 (2 x
1)
124
T4
355
(475)
1.2 1.6 1.3
32.000
(42.895)
- - - 175u3097
2 x 35 (2 x
1)
157
T4
400
(550)
1.2 1.4 1.2
36.000
(48.257)
- - - 175u3098
2 x 50
(2x1)
173
T4
450
(600)
1.1 (1.5) 1.3 1.1 (1.5)
42.000
(56.300)
- - - 175u3099
2 x 50
(2x1)
196
T4
500
(670)
0.9 1.1 (1.5) 2 x 1.9 - - - - - - -
T4
560
(750)
0.9 1.0 2 x 1.7 - - - - - - -
T4
630
(850)
0.8 0.9 2 x 1.5 - - - - - - -
T4
710
(950)
0.7 0.8 2 x 1.3 - - - - - - -
T4
800
(1075)
0.6 0.7 3 x 1.8 - - - - - - -
T4
1000
(1350)
0.5 0.6 3 x 1.6 - - - - - - -
Table 6.9 T4, Horizontal Braking 10% Duty Cycle, Recommended Brake Resistors
Type code and Selection Design Guide
MG20N622 Danfoss A/S © 09/2014 All rights reserved. 131
6 6