Adjustable frequency drive power and current ratings Filter current rating @690 V
Switching
frequency
Ordering number
525–600 V 551–690 V 525–550 V 50 Hz 60 Hz 100 Hz
IP00
IP20/23
1)
[kW (hp)] [A]
[kW
(hp)]
[A]
[kW
(hp)]
[A] [A] [A] [A] kHz
0.75 (1.0) 1.7 1.1 (1.5) 1.6 1.1 (1.5) 2.1
4.5 4 3 4 130B7335 130B7356
1.1 (1.5) 2.4 1.5 (2) 2.2 1.5 (2) 2.7
1.5 (2) 2.7 2.2 (3) 3.2 2.2 (3) 3.9
2.2 (3) 3.9 3.0 (4) 4.5 3.0 (4) 4.9
3 (4) 4.9 4.0 (5) 5.5 4.0 (5) 6.1
10 9 7 4 130B7289 130B73244 (5) 6.1 5.5 (7.5) 7.5 5.5 (7.5) 9.0
5.5 (7.5) 9 7.5 (10) 10 7.5 (10) 11
7.5 (10) 11 11 (15) 13 7.5 (10) 14 13 12 9 3 130B3195 130B3196
11 (15) 18 15 (2) 18 11 (15) 19
28 26 21 3 130B4112 130B4113
15 (20) 22 25 (18.5) 22 15 (20) 23
25 (18.5) 27 22 (30) 27 18 (24) 28
22 (30) 34 30 (40) 34 22 (30) 36
45 42 33 3 130B4114 130B4115
30 (40) 41 37 (50) 41 30 (40) 48
37 (50) 52 45 (60) 52 37 (50) 54
76 72 57 3 130B4116 130B4117*
45 (60) 62 55 (75) 62 45 (60) 65
55 (75) 83 75 (100) 83 55 (75) 87
115 109 86 3 130B4118 130B4119*
75 (100) 100 90 (125) 100 75 (100) 105
90 (125) 131 - - 90 (125) 137 165 156 124 2 130B4121 130B4124*
Table 6.24 Sine-wave Filters for Adjustable Frequency Drives with 525–600 V and 525–690 V
1) Ordering numbers marked with * are IP23.
Parameter Setting
14-00 Switching Pattern
[1] SFAVM
14-01 Switching Frequency
Set according the individual lter. Listed at lter product label and in output lter manual. Sine-wave lters do
not allow lower switching frequency than specied by the individual lter.
14-55 Output Filter
[2] Sine-wave lter xed
Table 6.25 Parameter Settings for Sine-Wave Filter Operation
Type code and Selection
Design Guide
MG20N622 Danfoss A/S © 09/2014 All rights reserved. 145
6 6