Parameter List and Menu Structure of VS 300
124
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
S Menu 3-1 System Configuration (CL2)
CONFIG POS: XXXXX Entry
Default
NT LT HP Dim.
No. Comp./Cond CL2 XX Number of compressors/fans (base load
stages) in CL2
With step control:
With speed control:
With combined control:
0 - max.
1)
1 or 2
min. 2-max.
1
)
2/4/6
1)
2/4/6
1)
2/4/6
1)
-
Cap.Stages CL2 XX Number of capacity stages each capacity-
controlled base load stage CL2
With step control:
With speed control:
With combined control:
1 - 3
1)
= 1
= 1
1 1 1 -
No.multist. CL2 XX Number of capacity-controlled base load
stages CL2
With step control:
With speed control:
With combined control:
0 - max.
1)
= 0
= 0
0 0 0 -
Enable CL2-stages → Enable/disable control stages in CL2 → See Screen 3-1-e
Stg.Ld.Shed. CL2 X Number of disabled relay/control stages
on load shedding CL2
0 - 3 0 0 0 -
Refrig. CL2 XXXXX → Select refrigerant in Control Loop 2 → See Screen 3-1-f
TRANSD.CL2 → Sensor matching Control Loop 2 → See Screen 3-1-g
Enab. tr CL2 Activate room/outside temperature analy
sis CL2 (only available with CAN Bus)
↑, ↓,
(ON/OFF)
OFF OFF OFF -
Enab.Humid.CL2 Activate analysis of air humidity ↑, ↓,
(ON/OFF)
OFF OFF OFF -
Node-Nr Env.CL2 CAN Bus node number of the VS
3000/VS 3000 BS from which CL2 draws
ambient data (humidity, outside/room
temperature)
1..9 - - - -
to-MinMon CL2 Activation of compressor shutdown by
shortfall relative to min. temperature CL1
(only LP control)
2)
4)
↑, ↓,
(ON/OFF)
ON ON - -
tc-MaxMon CL2 Activation of compressor shutdown by
shortfall relative to max. temperature CL2
(only HP control)
2)
↑, ↓,
(ON/OFF)
- - OFF -
Conumer.cont.CL2 → Select control by refrigeration point or
suction pressure Control Loop 2
3)
→ See Screen 3-1-h
Cons.nodeNo.CL2 Enter refrigeration point to control 2nd
control loop of pack
1 - 99 or --- -- -- -- -
forced ret. CL2XSelect oil equalization function Control
Loop 2
3)
↑, ↓, (N/Y) N N - -
Max. Off Time XXXm Enter maximum allowed run time before
forced shutdown
2)
.
Only shown when forced shutdown func
tion activated.
60..180 180 180 - min
Off Time XXXm Enter standstill time after forced shut
down
2)
.
Only shown when forced shutdown func
tion activated.
1..5 2 2 - min
No.AlRelays XXXX Number internal alarm relay 0..1 0 0 0 -