MANUAL ELDES ESIM264 V2.0 59
SMS
SMS text:
XXXX_M:ON
Example: 1111_M:ON
EKB2
Menu path:
OK → CONFIGURATION → PRIMARY SET →
POWER STATUS → CHECK EXT. PWR ST → ENABLE
EKB3
Enter parameter 13 & parameter status value:
[131#]
SMS
N/A
EKB2
Menu path:
OK → CONFIGURATION → PRIMARY SET →
POWER STATUS → AC FAILURE DELAY → [XXXXX]
Value: [XXXXX] – main power failure delay in seconds, range - [0... 65535]
EKB3
Enter parameter 70 & duration in seconds:
[70x#]
Value: x – main power failure delay in seconds, range - [0... 65535]
This command enables notications about main power status.
This command allows to set main power failure delay time period notifying all preset users
about external power supply loss events. If the power supply is restored during failure delay
time period, the system will not notify the user (-s) about this event. By default, this time
period is 30 seconds.
This parameter is useful when encountering temporary power supply failures.
Enable Main Power
Status SMS
Set Main Power
Failure Delay